WIRE SIZE vs. VOLTAGE DROP 


Max Wire Feet @ 120 Volts, 1 Phase, 2% Max Voltage Drop 
                                                                                                        Also see Ampacity Table for wire 

Amps Volt-Amps   #14 #12 #10 #8 #6
1 120   450 700 1100 1800 2800
5 600   90 140 225 360 575
10 1200   45 70 115 180 285
15 1800   30 47 75 120 190
20 2400   - 36 57 90 140
25 3000   - - 45 72 115
30 3600   - - 38 60 95
40 4800   - - - 45 72
50 6000   - - -

-

57

Amps Volt-Amps   #4 #2 1/0 2/0 3/0
1 120   4500 7000 - - -
5 600   910 1400 2250 2800

-

10 1200   455 705 1100 1400 1800
15 1800   305 485 770 965 1200
20 2400   230 365 575 725 900
25 3000   180 290 460 580 720
30 3600   150 240 385 490 600
40 4800   115 175 290 360 440
50 6000   90 145 230 290 360
60 7200   76 120 190 240 305
70 8400   65 105 165 205 260
80 9600  

-

90 144 180 230

Max Wire Feet @ 240 Volts, 1 Phase, 2% Max Voltage Drop

Amps Volt-Amps   #14 #12 #10 #8 #6
1 240   900 1400 2200 3600 5600
5 1200   180 285 455 720 1020
10 2400   90 140 225 360 525
15 3600   60 95 150 240 350
20 4800   - 70 110 180 265
25 6000   - - 90 144 210
30 7200   - - 75 120 175
40 5600   - - - 90 130
50 12000   - - -

-

105

Amps Volt-Amps   #4 #2 1/0 2/0 3/0
1 240   9000

-

-

-

-

5 1200   1750 2800 4500 5600 7000
10 2400   910 1400 2200 2800 3600
15 3600   605 965 1500 1900 2400
20 4800   455 725 1100 1400 1800
25 6000   365 580 920 1100 1440
30 7200   300 485 770 970 1200
40 5600   230 360 575 725 880
50 12000   180 290 460 580 720
60 14400   150 240 385 485 600
70 16800   130 205 330 415 520
80 19200   - 180 290 365 440
100 24000   - - 230 280 360
150 36000   - - 185 190 240
200 48000   - -

-

-

180